Technical Specifications
Protection
Overcurrent, Asymmetry and phase failure
Thermal setting Ir (A)
30...40
Rated Operational Voltage Ue (V)
690
Rated insulation voltage Ui (V)
690
tripping class
10
Frequency
0...400 Hz
Mounting
Direct on LS4K...LS18K
Auxiliary Contacts
1NO+1NC
Ith auxiliary contact in the base unit (A)
10
Connections
screw
Standard connection terminals
10 mm²
Torque
2,5 Nm
Storage temperature
-40/+70 °C
Operation temperature (°C)
-25...+60
Max backup fuse
63A aM; 100A gL-gG
Brand