CONTACTOR AEG 3NO 24VAC/DC 3 MOD.

VI403001

Contattore modulare AEG 40A, 3 contatti NO, potenza dissipata 6W, tensione di comando 24VAC/DC, tensione di isolamento 500V, tensione nominale di impiego 400VAC, temperatura di funzionamento -10/+50°C, temperatura di stoccaggio -40/+80°C, grado di protezione IP20, EN 61095

+

Downloads and Resources

Download informative and technical materials to learn more about the features of our products.

Click here for download: Product data sheet

Click here for download: Dimensioned drawing

Click here for download: Declaration RoHS

Click here for download: Deeplink REACH

Click here for download: Declaration DOC CE (Declaration of conformity CE)

Click here for download: Technical manual

Technical Specifications

Type

Modular Contactor

Rated Current (A)

40 A

Contacts

3NO

Control voltage (V)

24 AC/DC

Power loss

9 W

Rated insulation voltage Ui (V)

500

Rated Operational Voltage Ue (V)

400 AC

Rated current Ie in AC-7a (A)

40

Rated current Ie in AC-7b (A)

22

Mechanical life

1.000.000

Electrical Life (total operations) AC1/AC7a

60.000

Main Terminals Minimum Capacity (mmq)

2x1,5mm2

Main Terminals Maximum Capacity (mmq)

1x16mm2

Coil supply admissible range

85…110% Un

Operation temperature (°C)

-10/+50

Storage temperature

-40/+80 GC

Coil pick-up power at 50/60Hz or DC

4,5VA / 5W

Coil holding power at 50/60Hz or DC

4,5VA / 5W

Total closing time (ms)

<40

Total opening time (ms)

<40

Torque

2,5 NM

Mounting

any (except upside down)

Protection degree

IP20

Width

54 MM

Height

85 MM

Depth

65 MM

Standard

EN 61095