MCXT7

MCCB AEG MCXT7 3P 1250A 50KA EL. MI

MCXT7S31250MI

+

Downloads and Resources

Download informative and technical materials to learn more about the features of our products.

Click here for download: Product data sheet

Click here for download: Dimensioned drawing

Click here for download: Technical manual

Technical Specifications

Protection

Electronic Magnetic only Motor (SI)

Number of Poles

3

Rated Current (A)

1250 A

Ultimate breaking capacity Icu at 400/415V AC

50 kA

Ultimate breaking capacity Icu at 500 V AC

45 kA

Ultimate breaking capacity Icu at 690 V AC

30 kA

Service breaking capacity Ics (%Icu)

100%

Rated Operational Voltage Ue (V)

690 AC

Rated insulation voltage Ui (V)

1000

Category of use

B

Suitable for use as a isolator

YES

Overload channel LT

--

Time band classes LTD

--

Short-circuit channel ST

--

Time setting bands STD (s)

--

Instantaneus short-circuit protection channel I

Off, 1..10 In

Ground fault protection

--

Neutral protection

--

Mechanical life

20.000 operations

Electrical Life at In

3000 operations

Power loss

171 W

Standard connection terminals

50x20 mm²

Torque

18 Nm

Approvals

CE

State

On sale