MCXT3

MCCB AEG MCXT3 3P 63A 36KA TMD

MCXT3N3063

+

Downloads and Resources

Download informative and technical materials to learn more about the features of our products.

Click here for download: Product data sheet

Click here for download: Technical manual

Click here for download: Dimensioned drawing

Technical Specifications

Protection

Thermomagnetic Line

Number of Poles

3

Rated Current (A)

63 A

Ultimate breaking capacity Icu at 400/415V AC

36 kA

Ultimate breaking capacity Icu at 500 V AC

20 kA

Ultimate breaking capacity Icu at 690 V AC

5 kA

Ultimate breaking capacity Icu at 250 V DC

36 (2 poles in series) kA

Ultimate breaking capacity Icu at 500 V DC

_ kA

Service breaking capacity Ics (%Icu)

75%

Rated Operational Voltage Ue (V)

690 AC / 500 DC

Rated insulation voltage Ui (V)

800

Category of use

A (IEC 60947-2)

Suitable for use as a isolator

YES

Thermal setting Ir (A)

44...63

Magnetic setting Im

630 A

Neutral protection

100%

Mechanical life

25000 operations

Electrical Life at In

8.000 operations

Power loss

12,9 W

Standard connection terminals

24x8 mm²

Torque

8 Nm

Approvals

CE

State

On sale